Storage & Service
Storage
First turn your UPS OFF and disconnect its power cord from the wall outlet.
Then disconnect all equipment to avoid battery drain. If you plan on storing your
UPS for an extended period of time, fully recharge the UPS batteries once every
three months by plugging the UPS into a live AC outlet and letting the UPS
charge for 4 to 6 hours. If you leave your UPS batteries discharged for an
extended period of time, they will suffer a permanent loss of capacity.
Service
If returning your UPS for service, contact your local Tripp Lite dealer or
distributor. They will refer you to a service center. Please carefully pack the UPS
using the ORIGINAL PACKING MATERIAL that came with the unit. Enclose a
letter describing the symptoms of the problem. If the UPS is within the
warranty period, enclose a copy of your sales receipt.
Specifications
OMNISMART725
Output Capacity (VA/Watts): 725/425
Battery Runtime (Half Load/
Full Load) Minutes: 17/5
Battery Recharge Time: 2-4 hrs.
Approvals: UL, cUL, NOM
Modem/Fax Protection
(starts at 260V): 2 line
Input Voltage/Frequency (120V/60 Hz); On-Line Input Voltage Range (75 - 147 volts); Voltage-Regulated Output Voltage Range (120V +7%
/ -18%); On Battery Output Voltage Range (120V ±5%); Output Waveform Line Mode (filtered sinewave); Output Waveform Battery Mode
(PWM sine wave); AC Surge Suppression (exceeds IEEE 587 Cat. A & B standards); AC Noise Attenuation (>40 dB); AC Protection Modes
(H to N, H to G, N to G).
FCC Part 68 Notice (U.S. only)
If your Modem/Fax Protection causes harm to the telephone network, the Telephone Company may temporarily discontinue your service. If
possible, they will notify you in advance. If advance notice isn’t practical, you will be notified as soon as possible. You will be advised of your
right to file a complaint with the FCC. Your telephone company may make changes in its facilities, equipment, operations or procedures that
could affect the proper operation of your equipment. If it does, you will be given advance notice to give you an opportunity to maintain
uninterrupted service. If you experience trouble with this Modem/Fax Protection equipment, please contact the Manager of Technical Support,
Tripp Lite; 1111 W. 35th Street, Chicago, Illinois 60609; Phone: (773) 869-1234, for repair/warranty information. The telephone company may
ask you to disconnect this equipment from the network until the problem has been corrected or you are sure the equipment is not malfunctioning.
There are no repairs that can be made by the customer to the Modem/Fax Protection. This equipment may not be used on coin service provided
by the telephone company. Connection to party lines is subject to state tariffs. (Contact your state public utility commission or corporation
commission for information.)
FCC Radio/TV Interference Notice
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates,
uses and can radiate radio frequency energy, and if not installed and used in accordance with the instruction manual, may cause interference
to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by turning the device off and on, the user is encouraged to try
to correct the interference using one or more of the following measures: reorient or relocate the receiving antenna; increase the separation
between the equipment and receiver; connect the equipment into an outlet on a circuit different from that which the receiver is connected; consult
the dealer or an experienced radio/television technician for help. The user must use shielded cables and connectors with this product. Any
changes or modifications to this product not expressly approved by the party responsible for compliance could void the user's authority to
operate the equipment.