Tripp Lite AGSM1500XPSR3 Power Supply User Manual


 
Use the ON/OFF button to do three things:
Switch your UPS’s Operating Mode: While your UPS is plugged
into a live AC outlet, press the ON/OFF button and hold it until you
hear a beep (about 2 seconds) to toggle between the following operating
modes. Choose your UPS’s operating mode based on the regional
guidelines in Step 3 of the Quick Installation section.
• UPS Mode: ENABLES battery backup. UPS Conditions: The UPS
charges its battery and supplies power at its receptacles when it is
receiving utility line power. If utility power fails, the UPS provides
power from its batteries. The “ ” indicator light is lit. Setting
Advantages: Provides battery backup during blackouts or brownouts.
• CHARGE ONLY Mode: DISABLES battery backup. UPS
Conditions: The UPS charges its battery and supplies power at its
receptacles when it is receiving utility line power. The “ ” indicator
light is flashing. Setting Advantages: Continues to charge the battery
when power is present while turning OFF the inverter to prevent battery
depletion during power outages when equipment is not in use.
Cold-Start Your UPS: You may “cold start” your UPS and use it as a
stand-alone power source when utility power is not present, providing
that the UPS battery is charged. To “cold start” your UPS, press and
hold the ON/OFF button until you hear a beep (about 2 seconds), then
release it. The “ ” indicator light will illuminate and AC power
inverted from stored battery power will be provided at its receptacles.
Shut Down Your UPS: Press and hold the ON/OFF button when AC
line power is absent (i.e. during a blackout, or when the UPS is
unplugged) to deactivate your UPS.
Use the MUTE/TEST button to do two things:
Silence the UPS On-Battery Alarm: Press and hold this button to
silence the UPS On-Battery alarm, a series of short beeps followed by
a brief pause that is activated when the UPS is providing AC power
from battery. Note: When the battery is nearly depleted, the Low
Battery alarm—a continuous beep that cannot be silenced—will alert
you to immediately shut down connected equipment.
Run a Self-Test: Your UPS performs a self-test whenever it is first
plugged in. To have it run a self-test at another time, leave your
connected equipment on. With your UPS plugged in and in the UPS
mode, press and hold this button until you hear a beep (about 2 sec-
onds) then release it.
Results of a Self-Test: All the LEDs will be lit and the UPS will emit
several short beeps as it momentarily switches to battery to test its
charge and load capacity. The test will last at most 10 seconds. If the
inverter is overloaded, the “ ” LED will stay lit and the UPS will
continue to beep after the test; if this happens, remove some of the load
44
Basic Operation
5
These connections are optional. Your UPS will function properly without these connections.
USB Communications
Use any USB cable to connect the USB port of
your computer to the USB port of your UPS.
Download the PowerAlert UPS monitoring soft-
ware program appropriate for your operating
system from www.tripplite.com and install it on
your computer.
Serial Communications
(Select Models Only)
Use the serial cable provided with your UPS to
connect the DB9 port of your computer to the
DB9 port of your UPS. Download the
PowerAlert UPS monitoring software program
appropriate for your operating system from
www.tripplite.com and install it on your computer.
External Battery Connection
(Select Models Only)
External batteries are only needed to extend runtime.
Adding external batteries will increase recharge
time as well as runtime.
The illustration shows the location of your UPS’s
External Battery Connector, where you will
insert the battery pack cable. Complete installation
and mounting instructions for your battery pack
appear in the battery pack’s owner’s manual.
Make sure that cables are fully inserted into their
connectors. Small sparks may result during battery
connection; this is normal.
If you connect more than one external battery,
set the Charge Level switch to EXTERNAL
BATTERY. Your UPS’s charger will increase
its output to handle the additional batteries.
3
2
1
Quick Installation
optional
SEE MANUAL FOR
PROPER CONNECTION
NORM DELAY
EXTERNAL
BATTERY
Buttons
1
SEE MANUAL FOR
PROPER CONNECTION
NORM DELAY
EXTERNAL
BATTERY
2
SEE MANUAL FOR
PROPER CONNECTION
NORM DELAY
EXTERNAL
BATTERY
3
200310044 SmartPro XL Owner’s Manual 93-2078.qxd 10/9/2003 4:20 PM Page 4