Tripp Lite AVR Series Power Supply User Manual


 
Provides battery-derived AC output during blackouts, voltage boost during brownouts and voltage reduction during overvoltages
750VA/450 watt power-handling ability supports a variety of PCs, workstations and other sensitive electronics
Supports entry-level PC systems up to 35 minutes during blackout conditions
Built-in single-line Tel/DSL line surge suppression protects modems, fax machines or cordless phones
USB port, included USB cable and PowerAlert software offer safe, unattended shutdown without data loss during extended outages
HID-compliant USB port enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Supports Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot of application/OS or hard
power off/on reboot of connected equipment - ideal for unattended kiosk applications
Hot-swappable user battery replacement supported via battery access door
Space-saving, ultra-compact housing fits almost anywhere
Keyhole mounting flanges enable secure wallmount installation
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120VAC
Frequency
compatibility
60Hz
OUTPUT
Output VA 750
Output watts 450
Output nominal
voltage
120VAC
Output voltage
regulation
Sine wave 120V +8% / -21% (line mode) / PWM sine wave 115V +/-5% (battery mode)
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 12 NEMA 5-15R
INPUT
Maximum input amps 12A
Input connection type NEMA 5-15P (space saving right-angle plug)
Input cord length 6 ft / 1.8m
Recommended
Electrical Service
120V 15A
BATTERY
Full load runtime 3 min (750VA)
Half load runtime 10 min (375VA)
DC system voltage 12VDC
Typical battery
lifespan
3 to 6 years, depending on usage
Battery recharge rate 2 to 4 hours to reach 90% charge
Replacement Battery
Cartridge
RBC51
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation maintains 120V nominal over an input voltage range of 83V to 147V
Overvoltage
correction
Output voltage is reduced by 12% as line voltage increases to 128V or higher
Brownout correction Output voltage is boosted by 14% as line voltage decreases to 104V or lower
LEDS ALARMS & SWITCHES
Front panel LEDs 2 LEDs indicate line power, battery power status