Tripp Lite OMNI1000ISO Power Supply User Manual


 
Built-in surge suppression (backed by $200,000 Ultimate Lifetime Insurance) safeguards connected equipment against damage
SURGE VOLTAGE WITHSTAND CAPABILITY: ANSI/IEEE C62.41 Catagories A & B 6KV/200/500 amp 100Khz Ringwave and category B
BiWave
SURGE VOLTAGE ATTENUATION: N-G 2000:1, L-G 240:1, L-N 100:1
INSERTION LOSS: 65 db N-G from 10Khz to 100Khz, 45 to 60 db L-G from 10Khz to 100Khz, 18 to 54 db L-N from 50Khz to 500 Khz
6 UPS-supported AC outlets; 6-ft. cord
2-year product warranty
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V
Frequency
compatibility
60Hz
OUTPUT
Output VA 1000
Output watts 700
Output nominal
voltage
120V (line mode) / 115V (battery mode)
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-18%/+8%) / BATTERY MODE: 115V (+/-5%)
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz (+/-10%)
Outlet quantity / type 6 NEMA 5-15R
INPUT
Maximum input
amps
7.6A at 120V
Input connection
type
NEMA 5-15P
Input cord length 6 ft./1.8m
Recommended
Electrical Service
15A 120V
BATTERY
Full load runtime 8 min. (700W)
Half load runtime 24 min. (350W)
DC system voltage 36V
Typical battery
lifespan
4-6 years (typical)
Battery recharge rate 2-4 hours to 90%
Replacement
Battery Cartridge
RBC53
VOLTAGE REGULATION
Voltage regulation
description
Line-interactive UPS systems offers two levels of brownout correction and one level of overvoltage correction to
maintain usable, computer grade output
Overvoltage
correction
Input voltages between 128-143V are reduced by 9%
Brownout correction Input voltages between 96-107V are boosted by 10%
Severe brownout
correction
Input voltages between 85-95V are boosted by 20%
LEDS ALARMS & SWITCHES
Front panel LEDs 5 diagnostic LEDs indicate AC present, on battery, voltage correction status, overload and battery low/replace status