Tripp Lite OMNIX350HG Power Supply User Manual


 
Tripp Lite
1111 West 35th Street
Chicago, IL 60609 USA
Telephone: +(773) 869 1234
E-mail: saleshelp@tripplite.com
Model #: OMNIX350HG
Omni Smart UPS System - Line-interactive, medical-grade battery backup
Highlights
350VA line interactive tower UPS
Maintains sine-wave 230V nominal output over an input range of 159 to 266V
Professional features include USB port, IEC320 plug & outlets, built-in
isolation transformer
Input: IEC320 C14 inlet (230V) / Output: 6 IEC320 C13 (230V)
2 line phone suppression for TEL/DSL line protection
Description
Tripp Lite's OMNIX350HG offers medical-grade UPS protection with built-in line interactive voltage regulation, intelligent monitoring and unattended
shutdown capability. IEC320 plug & outlets, plus built-in isolation transformer with Faraday shield offers full isolation and removes common mode
noise. Tested to CE/IEC 60601-1 as medical electrical equipment. 350VA power handling capacity supports computers, inter-networking equipment
and other critical loads during commercial power failures. Line interactive voltage regulation corrects brownouts as low as 159V back to normal 230V
levels, saving battery reserves for use only during complete power failures. Includes, 2 line phone surge suppression and built-in USB
communications port that works with PowerAlert Software and cabling to provide automatic unattended shutdown of connected network and PC
applications.
Applications
Ideal UPS for protection of patient point of care solutions, wireless communications systems, electronic prescribing applications, medical imaging,
telemedicine and laboratory equipment. Units tested to CE/IEC 60601-1 provides ultimate safety and reliability for computer equipment used in
patient care areas and mission critical equipment. (Not recommended for life support applications.)
Package Includes
OMNIX350HG Hospital Grade UPS System
USB communication and telephone cables included
Warranty information
Instruction manual
Features
Ideal UPS protection for applications in medical patient-care areas where CE/ IEC 60601-1 electrical medical equipment is required
Line-interactive voltage regulation corrects brownouts as low as 159V without using battery power
IEC320 plug and outlets offer added degree of safety and reliability to input/output connections
Full line isolation prevents shock potential and operational problems in sensitive electronic equipment
Resistant to electrostatic discharge
Supports loads up to 350VA/225 watts
37 minutes half load runtime (with 175VA load), 15.5 minutes full load runtime (with 350VA load)
6 protected outlets; 6-inch dongle with IEC C14 inlet
1-USB port for monitoring interface