Tripp Lite SM2200RMNAFTA Power Supply User Manual


 
USB, serial and EPO cabling
Owner's manual with warranty information
Features
SmartPro line interactive UPS system is ideal for voice, data, medical and industrial networking applications
Line interactive Automatic Voltage Regulation (AVR) offers two levels of voltage boost during brownouts and one level of voltage cut during
overvoltages
Maintaints continuous operation through blackouts, voltage fluctuations and surges
Corrects line voltage conditions as low as 83V and as high as 145 back to selectable 100/110/120V nominal values
Standard internal battery set offers 16 minutes at half load (800w) and 6 minutes at full load (1600w)
Optional BP48V24-2U and BP48V60RT3U external rack/tower battery packs enable extended runtime operation
Compact rackmount form factor installs using only 2 rack spaces (2U) with a maximum installed depth of only 19 inches
Ships with all mounting accessories for 4 post rackmount installation
Optional 2POSTRMKITWM enables 2 post rackmount or wallmount installation
Optional 2-9USTAND accessory enables small-footprint upright tower placement
Network interfaces support simultaneous communications via built-in USB, DB9 serial and SNMPWEBCARD slot
HID compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, with
the built-in ability to shutdown any number of additional servers over IP
UPS interface supports on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge current,
battery capacity, AC line frequency, timed inverter sutoff, activate self-test, load bank output power control and remote reboot
Built-in Emergency Power Off (EPO) interface with cable
NEMA 5-20P input plug (user-installable NEMA 5-15P replacement plug included) / NEMA 5-15R & NEMA 5-15/20R output receptacles
Integrated 3 bank switched PDU enables remote outlet management for load shedding or remote reboot of individual load banks (Each
bank controls 1 outlet per load bank)
Front panel LEDs offer current monitoring and battery charge level information
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user required
2 year manufacturer's product warranty, $250,000 ULtimate Lifetime Insurance
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V factory default (110V, 100V user selectable)
Frequency
compatibility
50 / 60 Hz
OUTPUT
Output VA 2200
Output watts 1600
Output nominal
voltage
120V (110V, 100V) VAC
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-18% / +8%)
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10%
Outlet quantity / type 4 NEMA 5-15R and 4 NEMA 5-15/20R
Customized load
management
receptacles
3 single outlet load banks
INPUT
Maximum input amps 13.3 (120V)/ 14.6 (110V)/ 16.0 (100V)
Input connection type NEMA 5-20P (optional, user-installable NEMA 5-15P included in box)