Tripp Lite SMART1000RM2U Power Supply User Manual


 
Features
SMART 1000RM2U line interactive UPS offers battery derived sine wave AC output during power outages, voltage regulation during
brownouts and overvoltages, plus network grade AC surge suppression
1000VA/700 watt power handling capability with full-time sine wave output offers guaranteed compatibility with networking, telecom and
other sensitive electronic devices
Supports 2U rackmount installation in 4 post rack enclosures with included mounting accessories, 2 post rackmount mountable with optional
2POSTRMKITWM accessory, upright tower installation supported with optional 2-9USTAND accessory
Large internal batteries offer runtimes of 17 minutes at half load (500VA/350 watts) and 7 minutes at full load (1000VA/700 watts)
Maintains regulated 120V nominal output during brownouts and overvoltages from 83 to 147V
Includes 6 UPS-supported outlets arranged in 2 individually controllable load banks (2 outlets per bank) that can be powered off and back
on again via software interface
PowerAlert UPS monitoring and unattended shutdown software enables configurable network broadcast messaging, email notification,
event logging and running user-defined script commands
Offers simultaneous monitoring by up to 3 directly-connected devices through included USB, DB9 and SNMP* interfaces (*requires optional
SNMPWEBCARD), or the monitoring of any number of additional UPS systems over IP with included PowerAlert monitoring software.
Communications ports support messaging of UPS and line power status, including on-battery, low-battery, power restored, AC line voltage,
DC battery voltage and remaining battery capacity
Supports timed inverter shutoff after unattended shutdown, activate self-test and UPS output power control for delayed or immediate reboot
of connected devices
Supports Tripp Lite's WatchDog software application to restore unresponsive programs by systematically restarting applications, operating
systems and ultimately rebooting completely locked computers by momentarily switching UPS power off and back on again (requires
optional WATCHDOGSW)
Built-in accessory slot supports SNMP with optional SNMPWEBCARD adapter
Emergency Power Off (EPO) interface with cable
Multi-function audible alarms and set of 5 front panel LEDs
Network-grade AC surge suppression
Attractive all-black color scheme
UPS battery set ships fully assembled and ready for installation, no time consuming connection of internal batteries by user is necessary
Two year warranty with $250,000 connected equipment insurance (USA & Canada only)
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120V AC
Frequency
compatibility
60 Hz
OUTPUT
Output VA 1000
Output watts 700
Output nominal
voltage
120V AC
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-21% +8%), BATTERY MODE: Sine wave output within 5% of 120VAC
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 6 NEMA 5-15R
Customized load
management
receptacles
"Includes 2 load banks, each with 2 outlets, that support load shedding and remote reboot on demand of locked network
devices. Controllable via PowerAlert software to automatically switch off optional loads, like monitors, to increase
available runtime for servers and other critical devices. "
Overload protection 15A input breaker
INPUT
Maximum input
amps
6.8A / 770 watts
Input connection
type
NEMA 5-15P