Tripp Lite SMART700DVA Power Supply User Manual


 
network workstations
Includes 6 UPS-supported outlets
Supports remote monitoring of UPS and site power conditions via built-in USB and RS-232 enabled DB9 ports
Works with PowerAlert UPS monitoring and unattended shutdown software, available via free download from www.tripplite.com
Includes complete USB and serial cabling
Built-in audible alarm and 5 front panel LEDs indicate status of line power, battery power, battery low/replace, voltage regulation and load
level
Network-grade AC surge suppression protects equipment from damage and performance problems resulting from transient surges
2-year warranty
3 and 5 year extended warranty options available
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120 or 230V AC
Frequency
compatibility
50/60 Hz (UPS does not convert frequency)
OUTPUT
Output VA 700
Output watts 450
Output nominal
voltage
120V AC
Output voltage
regulation
120V (+8% / - 21%)
Output frequency
regulation
Passes line frequency of 50 or 60Hz +/-10%
Outlet quantity / type 6 NEMA 5-15R
Overload protection Input circuit breaker
INPUT
Maximum input amps 4.8A @ 120V (2.6A @ 230V)
Input connection type C14 inlet
Input cord length Includes NEMA 5-15P to C13 inlet
BATTERY
Full load runtime 11 min.
Half load runtime 27.5 min.
DC system voltage 24VDC
Typical battery
lifespan
4-6 years
Battery recharge rate 2-4 hours (to 90%)
Replacement Battery
Cartridge
Qty 4 - RBC51
VOLTAGE REGULATION
Voltage regulation
description
Automatic voltage regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without
using battery power, during brownouts to 83V and overvoltages to 147V (120V) / 159V to 282V (230V)
Overvoltage
correction
Overvoltages from 125V to 147 V (120V) and from 240V to 282V (230V) are reduced by 12%
Brownout correction Undervoltages from 83V to 104V (120V) and from 159V to 199V (230V) are boosted by 14%
LEDS ALARMS & SWITCHES
Front panel LEDs Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE
REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information