Voltage regulation
description
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using
battery power, during brownouts to 75V and overvoltages to 147V
Overvoltage
correction
Input voltages between 128 and 147VAC are reduced by 12%
Direct pass
through
Input voltages between 108 and 127VAC are passed on to connected equipment unchanged
Brownout
correction
Input voltages between 93 and 107VAC are boosted by 14%
Severe brownout
correction
Input voltages between 75 and 92VAC are boosted by 30%
LEDS ALARMS & SWITCHES
Front panel LEDs Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE
REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
Alarms Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel
alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches Includes 2 front panel switches - one main on/off power switch and one dual function "alarm cancel" / "self test" button
SURGE / NOISE SUPPRESSION
AC surge
suppression
480 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight
(lbs)
23.5
Shipping weight
(kg)
10.7
Shipping
Dimensions
(HWD/in)
15 x 11.25 x 10.75
Shipping
Dimensions
(HWD/cm)
38.1 x 28.6 x 27.3
Unit weight (lbs) 21
Unit weight (kg) 9.5
Unit Dimensions
(HWD/in)
11.75 x 7.25 x 7.75
Unit Dimensions
(HWD/cm)
29.8 x 18.4 x 19.7
Material of
construction
Polycarbonate
Form factors
supported
Tower
Cooling method Convection
Battery Access Battery access door allows user replacement of UPS batteries
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage
Temperature
+5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius