Tripp Lite SMART700USB Power Supply User Manual


 
Voltage regulation
description
Line interactive voltage regulation corrects brownouts as low as 83V back to 120V nominal values
Brownout correction Input voltages between 83 and 105 are boosted by 14%
Direct pass through Voltages of 106V and greater are passed through to connected equipment unchanged
LEDS ALARMS & SWITCHES
Alarms Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches Includes 2 front panel switches — one main on/off power switch and one dual function "alarm cancel" / "self test"
button
Front panel LEDs 4 LEDs indicate performance conditions:
GREEN "online"
GREEN "voltage regulation enabled"
RED "on battery"
YELLOW "battery low/replace"
SURGE / NOISE SUPPRESSION
UPS AC suppression
joule rating
Conforms to IEEE 587 / ANSI C62.41 specifications
EMI / RFI AC noise
suppression
Yes
AC suppression
response time
Instantaneous
Dataline suppression Single line TEL/DSL or network ethernet surge suppression via single pair of RJ-style 8 position jacks (ethernet
protection pins 1,2,3,6 - 7.5V clamping / phone protection pins 4,5 - 260V clamping), includes phone cable
PHYSICAL
Shipping weight (lbs) 18.6
Shipping weight (kg) 8.4
Cooling method Convection
Unit Dimensions
(HWD/in)
10.75 x 5.25 x 7.25
Unit Dimensions
(HWD/cm)
27.3 x 13.3 x 18.4
Unit weight (lbs) 17.2
Unit weight (kg) 7.8
Material of
construction
PVC
Form factors
supported
Tower, wall mountable with optional UPSWM accessory
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
COMMUNICATIONS
WatchDog
compatibility
Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft
reboot of application / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk
applications
Network monitoring
port
Built-in USB port supports on battery, low battery, and power restored messaging