BATTERY
Full load runtime 4 min. (10,000VA/8000W)
Half load runtime 10 min. (5000VA/4000W)
Connects to UPS via Included 3-wire DC cable
DC system voltage 240VDC
Typical battery
lifespan
4-6 years
Battery recharge rate Less than 8 hours to 90% (included battery set only)
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected
nominal voltage at all times
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within
2% of selected nominal
Brownout correction Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC,
regulating output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs 6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. LED/LCD display panel easily
rotates for better viewing in rackmount or tower configurations.
Alarms Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter
fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete
Switches Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 402
Shipping weight (kg) 181
Shipping Dimensions
(HWD/in)
49.3 x 23 x 31.5
Shipping Dimensions
(HWD/cm)
125.1 x 58.4 x 80
Unit weight (lbs) Power Module (54.8), Step-down Transformers (60), Battery Pack (158.7)
Unit weight (kg) Power Module (24.7), Step-down Transformers (27), Battery Pack (71.4)
Unit Dimensions
(HWD/in)
Power Module 5.14 x 17.5 x 25, Step down transformers 3.5 x 17.5 x 20.8, Battery Pack 5.16 x 17.5 x 25 (Installed
depth of power module extends to 32.5 inches once detachable PDU backplate is installed)
Unit Dimensions
(HWD/cm)
Power Module 13.3 x 44.4 x 63.5, Step down transformers 8.9 x 44.5 x 52.7, Battery Pack 13.4 x 40.6 x 63.5 (Installed
depth of power module extends to 82.6 cm once detachable PDU backplate is installed)
Material of
construction
Steel
Form factors
supported
Rack (10U)
Cooling method Fan
Battery Access User replaceable, hot swappable external battery pack
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius