Output frequency
regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type -
INPUT
Maximum input amps 200V - 46.7A / 208V - 44.9A / 220V - 42.4A / 230V - 40.6 / 240V - 38.8A
Input connection type -
BATTERY
Full load runtime n/a
Half load runtime n/a
DC system voltage 240VDC
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected nominal
voltage at all times
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within
2% of selected nominal
Brownout correction Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156V AC,
regulating output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs 6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. LED/LCD display panel easily
rotates for viewing in rackmount or tower configurations.
Alarms Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter
fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete
Switches Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 91.6
Shipping weight (kg) 41.6
Shipping
Dimensions (HWD/in)
11.25 x 31.5 x 23
Shipping
Dimensions
(HWD/cm)
28.6 x 80 x 58.4
Unit weight (lbs) 57.2
Unit weight (kg) 26
Unit Dimensions
(HWD/in)
5.25 x 17.5 x 26
Unit Dimensions
(HWD/cm)
13.3 x 44.4 x 66
Material of
construction
Steel
Form factors
supported
Rack (3U)
Cooling method Fan
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing