Tripp Lite SU1000RTXL2UA Power Supply User Manual


 
Outlet quantity /
type
6 NEMA 5-15R
Customized load
management
receptacles
2 single outlet controllable load banks support load shedding and remote reboot on demand of locked network devices.
Overload
protection
15A input breaker
INPUT
Maximum input
amps
8.6A
Input connection
type
NEMA 5-15P
Input cord length 10 ft. 14 gauge
Recommended
Electrical Service
15A 120V
BATTERY
Full load runtime 4.5 minutes with internal batteries (800 watts)
Half load runtime 14 minutes with internal batteries (400 watts)
Expandable
battery runtime
Supports extended runtime with optional external battery packs BP24V15RT2U (limit 1), BP24V28-2U (limit 1) and
BP24V70-3U (multi-pack compatible)
DC system voltage 24VDC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge
rate
Less than 6 hours to 80%
Replacement
Battery Cartridge
RBC92-2U
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion power conditioning maintains output within 2% of 100/110/120 volts at all times
Overvoltage
correction
Maintains output of selected nominal +/-2% during overvoltages to 138V AC
Brownout
correction
Maintains output of selected nominal +/-2% during undervoltages to 65V AC (at loads greater than 70% undervoltage
correction extends to 80V)
LEDS ALARMS & SWITCHES
Front panel LEDs LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red), battery
low (yellow) - 4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%). LED display panel easily rotates for
better viewing in rackmount or tower configurations.
Alarms Multi-function audible alarm with distinctive ring patterns offer notification of backup operation (2 seconds on / 0.5 seconds
off), low battery warning (1.25 seconds on / 0.5 seconds off), overload (sounds continuously), UPS fault (4.2 seconds on /
1 second off), input voltage out of frequency (2.1 seconds on / 0.14 seconds off) and high input voltage (2.1 seconds on
0.07 seconds off)
Switches Includes power off/on switch to enable system turn on (press ON switch), UPS battery test (press ON switch during normal
AC operation), buzzer silence (press ON switch during battery operation) and OFF (press OFF switch) - all switch functions
require that the switch be pressed and held for longer than 2 seconds, but less than 4 seconds
SURGE / NOISE SUPPRESSION
AC surge
suppression
480 joules
AC suppression
response time
Instantaneous
Dataline
suppression
Set of 8 wire RJ style interface jacks offer surge suppression for network ethernet or TEL/DSL connection. Pins 1,2,3 and
6 offer ethernet protection starting at 7.5V and the center two wires, pins 4 & 5, offer TEL/DSL line suppression starting at
260V