Tripp Lite SU1000RTXLCD2U Power Supply User Manual


 
4 post installation hardware included, Optional 2POSTRMKITWM enables 2 post rack / wallmount installation, Optional 2-9USTAND
enables tower placement
Single line TEL / Network surge suppression
Electronic bypass maintains utility output during a variety of UPS fault conditions
Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries
are expired and require replacement
Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60
to 50Hz
Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
Included PowerAlert UPS monitoring software
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
1000
Output kVA
capacity (kVA)
1
Output Watt
Capacity (watts)
900
Output power
factor
0.9
Output Capacity
Details
ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120/115/110V
900 watts, 100V 810 watts). FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are
reduced in frequency regulation / conversion mode (127/120/115/110V 630 watts / 100V 567 watts).
Crest Factor 3:1
Nominal Output
Voltage(s)
Supported
100V; 110V; 115V; 120V; 127V
Nominal Voltage
details
120V factory-default nominal voltage
Frequency
compatibility
50/60 Hz (auto-selectable); Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency
compatibility
details
ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output
matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds
+/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY
REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency input is 40 to
70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is
regulated to +/-0.05Hz.
Output voltage
regulation (line
mode)
+/- 2%
Output voltage
regulation
(Economy line
mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 3%
Built-in UPS
output receptacles
6 5-15R outlet(s)