Tripp Lite SU12000RT4U Power Supply User Manual


 
Output circuit breaker 20A branch rated double pole breakers (x3) protect 2 C19 and 1 5-15/20R outlets each, 30A branch rated double
pole breakers (x2) protect 1 L6-30R outlet each, 20A single pole breakers (x2) protect one 5-15/20R outlet each
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current (at
maximum load)
50A
Nominal Input
Voltage(s) Supported
208V AC / 120V AC (4 wire split single phase); 240V AC /120V AC (4 wire split single phase)
UPS input connection
type
Hardwire
UPS input connection
description
4 wire split-phase input (L1, L2, N, G)
Recommended
Electrical Service
50A 208/240-120 Split Phase
Phase Single-Phase
BATTERY
Full load runtime
(minutes)
7 min. (8400w)
Half load runtime
(minutes)
20 min. (4200w)
Expandable battery
runtime
Supports extended runtime with optional external battery packs
External battery pack
compatibility
BP192V18-4U; BP192V557C-16K; BP192V787C-16K; BP192V1037C-16K; BP192V1407C-16K
DC system voltage
(VDC)
192
Battery recharge rate
(included batteries)
Less than 6 hours from 10% to 80%
Battery replacement
description
Hot-swappable, user replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Online, double-conversion power conditioning
Overvoltage correction 3% output voltage regulation during overvoltages to 140 (measured L1-N : L2-N)
Undervoltage
correction
3% output voltage regulation during undervoltages to 65 (measured L1-N : L2-N)
LEDS ALARMS & SWITCHES
LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD
screen offers additional information and control options
Alarms Unique audible alarms for all major UPS, environmental and power conditions (see manual)
Alarm cancel operation Alarm cancel switch