Tripp Lite SU1500RTXL2U Power Supply User Manual


 
DC system voltage
(VDC)
48
Battery Access User replaceable, hot swap battery replacement supported via front access panel
Full load runtime Internal batteries — 5 min. /1 BP48V212U battery pack (1500VA) — 28 min.
Half load runtime Internal batteries — 17 min. / 1 BP48V212U battery pack (750VA) — 74 min.
Battery Pack
Accessory
(optional)
BP48V212U (optional)
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge
rate
2-4 hours to 90%
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion power conditioning maintains output within 2% of 120 volts at all times
Overvoltage
correction
Maintains output of 120V +/-2% without consuming battery power during overvoltages to 138V AC
Brownout
correction
Maintains output of 120V +/-2% during undervoltages to 80V AC
Severe brownout
correction
At load levels less than 70%, UPS maintains output of 120V +/-2% during undervoltages to 65V AC
LEDS ALARMS & SWITCHES
Alarms Multi-function audible alarm offers notification of UPS start, backup operation, low battery warning, overload, UPS fault
and remote shutdown
Switches Includes main power off/on switch, plus 1 switch to select battery charge / load level display
Front panel LEDs 6 LED STATUS DISPLAY: line power (green), online (green), bypass (yellow), on battery (green), overload (red),
battery low (yellow)
4 LED LOAD / BATTERY LEVEL DISPLAY (100%, 75%, 50%, 25%)
SURGE / NOISE SUPPRESSION
UPS AC
suppression joule
rating
2440 joules
EMI / RFI AC noise
suppression
Yes
AC suppression
response time
Instantaneous
PHYSICAL
Shipping weight
(lbs)
63.8
Shipping weight
(kg)
29.0
Cooling method Built-in cooling fan
Unit Dimensions
(HWD/in)
3.5 x 17.5 x 22
Unit Dimensions
(HWD/cm)
8.89 x 44.5 x 52.8