Tripp Lite SU1500RTXL2UHV Power Supply User Manual


 
Storage and Service
First turn your UPS OFF: press the “OFF” switch to turn power off at the UPS outlets, then
disconnect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery
drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS
batteries once every three months by plugging the UPS into a live AC outlet and letting the
UPS charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period
of time, they may suffer permanent loss of capacity.
If returning your UPS to Tripp Lite, please carefully pack the UPS using the ORIGINAL
PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the
problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.
Storage
Service
Specifications
All Models: Input Frequency (50/60 Hz Auto-Selecting); Output Waveform in Line and Battery Modes (Pure Sine Wave);
Transfer Time: (0 ns.); Maximum Harmonic Distortion with Linear Load (< 3%); Maximum Harmonic Distortion with
Nonlinear Load (< 6%); Battery Recharge Time to 80% Capacity (2-4 hours).
Model SU1000RTXL2U SU1000RTXL2UHV SUINT1000RTXL2U
Input Voltage (< 70% Load): 65-138V 130-275V 130-275V
Input Voltage (Full Load): 80-138V 160-275V 160-275V
Output Voltage: 120V 208V 230V
Input Breaker Rating: 15A 8A 8A
Input Plug Type: 5-15P 6-15P IEC 320-C14
Recommended Utility Amps: 15A 15A 10A
Output Capacity (VA/Watts): 1000/800 1000/800 1000/800
Battery Runtime (Half Load/Full Load) Min.: 18/6 18/6 18/6
System Battery Voltage: 36 VDC 36 VDC 36 VDC
Approvals: UL, cUL, FCC, NOM UL, cUL, FCC, NOM CE
Model: SU1500RTXL2U SU1500RTXL2UHV SUINT1500RTXL2U
Input Voltage (< 70% Load): 65-138V 130-275V 130-275V
Input Voltage (Full Load): 80-138V 160-275V 160-275V
Output Voltage: 120V 208V 230V
Input Breaker Rating: 20A 10A 10A
Input Plug Type: 5-15P 6-20P IEC 320-C14
Recommended Utility Amps: 20 A 15 A 15 A
Output Capacity (VA/Watts): 1500/1200 1500/1200 1500/1200
Battery Runtime (Half Load/Full Load) Min.: 17/5 17/5 17/5
System Battery Voltage: 48 VDC 48 VDC 48 VDC
Approvals: UL, cUL, FCC, NOM UL,cUL, FCC, NOM CE
Model SU2200RTXL2U SU2200RTXL2UHV SUINT2200RTXL2U
Input Voltage (< 70% Load): 65-138V 130-275V 130-275V
Input Voltage (Full Load): 80-138V 160-275V 160-275V
Output Voltage: 120V 208V 230V
Input Breaker Rating: 30A 15A 15A
Input Plug Type: 5-20P 6-20P IEC 320-C20
Recommended Utility Amps: 20A 20A 20A
Output Capacity (VA/Watts): 2200/1600 2200/1600 2200/1600
Battery Runtime (Half Load/Full Load) Min.: 18/6 18/6 18/6
System Battery Voltage: 48 VDC 48 VDC 48 VDC
Approvals: UL, cUL, FCC, NOM UL, cUL, FCC, NOM CE
14