Tripp Lite SU16KRT8 Power Supply User Manual


 
Supports Emergency Power Off (EPO) via built-in interface
Front panel LEDs and LCD readout with scroll controls
LED / LCD display panel rotates for viewing in rackmount or tower configurations
External battery packs are field replaceable and hot swappable
Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
Specifications
OUTPUT
Output Volt Amp
Capacity (VA)
16000
Output kVA capacity
(kVA)
16
Output Watt
Capacity (watts)
14400
Output kW capacity 14.4
Output power factor 0.9
Output Capacity
Details
Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30
seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power;
Double conversion mode is automatically restored as load levels are reduced to 95% or less
Nominal Output
Voltage(s) Supported
200V; 208V; 240V
Nominal Voltage
details
Voltage selection via front panel LCD interface
Frequency
compatibility
50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
Frequency
compatibility details
Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to
50Hz or 50Hz to 60Hz (no de-rating)
Output voltage
regulation (line
mode)
+/- 2%
Output voltage
regulation (Economy
line mode)
+/- 10%
Output voltage
regulation (Battery
mode)
+/- 2%
Built-in UPS output
receptacles
8 L6-20R outlet(s); 2 L6-30R outlet(s)
Output circuit
breaker
8 20A breakers protect one L6-20R outlet each, 2 30A breakers protect one L6-30R outlet each
Output AC waveform
(AC mode)
Sine wave
Output AC waveform
(battery mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
92A (200V), 88.4A (208V), 83.6A (220V), 80A (230V), 76.6A (240V)
Nominal Input
Voltage(s) Supported
200V AC; 208V AC; 240V AC