Tripp Lite SU20K3/3 Power Supply User Manual


 
Recommended
Electrical Service
120/208V AC (3-Phase, 4 Wire, wye)
BATTERY
Full load runtime Included internal batteries: 5 min. (16,000 watts). Runtime can be extended with additional internal battery packs (model #
SURBC2030).
Half load runtime Included internal batteries: 17 min. (8,000 watts). Runtime can be extended with additional internal battery packs (model #
SURBC2030).
Expandable
battery runtime
Supports extended runtime with optional internal battery packs (model # SURBC2030). Accepts 2 additional internal
battery packs. Build to order expandable runtime systems are available. Standalone external battery module (SUBF2030)
and built-to-order systems also available.
DC system voltage 240V DC
Typical battery
lifespan
3 - 6 years, depending on usage
Battery recharge
rate
2 - 4 hours to 90%
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion process gives this UPS the ability to maintain output voltage within +/-2% of nominal voltage at
all times
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 144 / 250V AC (3-Phase, 4-Wire, wye),
reducing output within 2% of nominal
Brownout
correction
Maintains continuous operation without using battery power during brownout / undervoltage conditions to 88 / 166V AC
(3-Phase, 4-Wire, wye)
LEDS ALARMS & SWITCHES
Front panel LEDs 7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, bypass operation and battery
operation. SELECTABLE LCD DISPLAY: indicates a wide range of UPS operational and fault/warning conditions
including operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage
and more.
Alarms Alarms warn against a variety of operational conditions: low battery, overload, shutdown, bypass and more
Switches ON button turns UPS's inverter ON. OFF button turns UPS's inverter OFF. Select Button browses through items displayed
on LCD screen. Enter button selects items displayed on LCD screen. Select and Enter buttons used simultaneously mute
UPS alarms. Battery Start Switch cold starts the inverter. Emergency Power Off button turns UPS output OFF and
disables Bypass output. Manual Bypass switch bypasses the UPS's inverter during maintenance.
SURGE / NOISE SUPPRESSION
AC surge
suppression
480 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight
(lbs)
609
Shipping weight
(kg)
276
Shipping
Dimensions
(HWD/in)
43 x 28 x 44.5
Shipping
Dimensions
(HWD/cm)
109.2 x 71.1 x 113
Unit weight (lbs) 520
Unit weight (kg) 236
Unit Dimensions
(HWD/in)
35.3 x 19.3 x 36