Tripp Lite SUIOK Power Supply User Manual


 
UPS LOCATION
Move your UPS over short distances using its wheels. Stabilize the UPS by releasing the
stabilizers on each side of the unit. NOTE: Do not stack the UPS Systems or external
battery packs.
INPUTAND OUTPUT CONNECTION
WIRING
SELECTION
Choose appropriate cabling (depending on current carried; see chart below) to connect
your UPS to an AC power supply and your equipment to your UPS:
WIRING
CONNECTIONS
Connect your wiring to the input and output terminal blocks located on the lower rear
panel of your UPS (see figure below). Before cable connection, turn the UPS
OFF
and pull
out the fuse holder. Ensure the cable is fitted with a cable sleeve and
is
secured by a
connector clamp. The minimum tightening torque is
35
Ibs. per square inch. Connect
the ground wire (typically colored green and yellow) to the terminal marked with the
letter "G."
MODEL
SU6K
SU
IOK
Cable Connection for
6kVA
or
lOkVA
Output
(6kVA
shown)
AC
INPUT
156-264V50/60HZ
RATED
INPUT
CURRENT
208/240
I0
3 Wlre
30A 8 AWG (8mm1/60"C)
50A6AWG (14mrn1/60"C)
LUOV
CAUTION: Observe the appropriate
cable connection regulations
1e.g.
GROUND
UPS
National Electrical Code (NEC) in
CONNECTION
the U.S.] at all times. Using cables
TOTH,"AEkDING
of improper size may damage your
(GROUND)
equipment and cause fire hazards.
+
Ground the UPS and the load
equipment as shown in the figure.
LOAD
1
LOAD
2
LOAD
3
RATED
OUTPW
CURRENT
120-208/240V 103 Wlre
30A 8 AWG (8mm1/6W)
50A6AWG (14mm2/60"C)
RATED
OUE'UT
CURRENT
120V 103Wlre
2
x
32A 6 AWG [14rnm1/60"C)
2
x
50A4 AWG (22mmv/6(PC)
OUTPUT
PROTECnON
CIRCurr
32A
63A