Tripp Lite Switched Rack PDU Power Supply User Manual


 
6
Features
Input Plug Adapter (Select Models): Converts the twist-lock
input plug to a straight-blade input plug.
Power Inlet (Select Models): The IEC power inlet connects to
the included power cord or a compatible user-supplied power
cord. The inlet includes a bracket to secure the cord connection.
Outlets (Vary by Model): During normal operation, the outlets
distribute AC power to connected equipment. When an outlet is
live, the associated LED illuminates.
Outlet LED: Each outlet LED illuminates when the associated
outlet is ready to distribute live AC power. The IEC-60320-C19
outlets are arranged in pairs, and there are 2 LEDs below each
pair. The LED to the left is associated with the upper outlet .
The LED to the right is associated with the lower outlet .
Other outlet types have an LED directly below each outlet.
Digital Load Meter (Ammeter): The total connected equipment
load is displayed on the meter in amperes. Models with
multiple outlet banks can also display the connected equipment
load for each outlet bank. Use the mode selection switch to
display the total load (all bank LEDs illuminated) or the load
for each outlet bank (corresponding bank LED illuminated).
Circuit Breaker (Select Models): If the connected equipment load
exceeds the Maximum Load Rating of the PDU, the circuit breaker
will trip. Disconnect excess equipment and allow the breaker to cool
before depressing the plunger to reset the breaker. Models with
multiple outlet banks have a circuit breaker for each bank.