3. Multiply the voltage and current of each piece of equipment (VA requirements); for
example, 120V x 2.7A = 324VA, 120V x 2.0A = 240VA.
Add up the VA requirements for
all the devices; for example, 324VA + 240VA =
564VA.
4. Make sure that your UPS has at least as much VA capacity as your equipment
requires.
3.4 Powering Up Your UPS
1. For 100/110V/120V versions, connect the power cord to a grounded 3-wire
receptacle. For 220V/230V/240V versions, please refer to Sec 3.5 .
2. Power up the UPS by pressing the On/Off switch on the front panel for three
seconds.
3. We recommend that you charge the battery for six (6) hours before first use of your
UPS. You may use the UPS immediately without charging the battery, but the
backup time may be less than the rating. The UPS recharges the battery
automatically whenever AC power is available.