Specifications
Power
24Vı(ac/dc), +10/-15 percent, 50/60Hz, ±5 percent
12VA maximum power consumption
Data retention upon power failure via nonvolatile memory
Environment
0 to 65°C (32 to 149°F) operating temperature
-40 to 85°C (-40 to 185°F) storage temperature
0 to 90 percent RH, non-condensing
Accuracy
Calibration accuracy and sensor conformity: ±0.1 percent of
span, ±1°C @ the calibrated ambient temperature and rated
line voltage
Calibration ambient temperature = 25°C ±3°C (77°F ±5°F)
Accuracy span: 540°C (1000°F) minimum
Temperature stability: ±0.1°C/°C (±0.2°F/°F) rise in ambient
maximum
Agency Approvals
•UL
®
508, C-UL
®
, CSA and CE
ODVA: EtherNet/IP
Controller
Microprocessor-based user-selectable control modes
Single or dual channel universal inputs
Current transformer inputs/digital inputs
Up to four programmable outputs
Update rates, inputs = 10Hz, outputs = 10Hz
Operator Interface
Browser based HMI
Wiring Termination
Touch safe removable terminals
14 to 22 AWG
Universal Inputs (Electrically Isolated)
Thermocouple, grounded or ungrounded sensors
RTD 2 or 3-wire, platinum, 100
@ 0°C calibration to
DIN curve (0.00385
//°C)
Process 0-20mA @ <100
, or 0-10VÎ(dc) @ 10k input
impedance (50,000 bits @ full scale)
Digital Inputs
Contact or dc voltage
10K
input impedance
Current Transformer Inputs
0 to 50mA CT input into 100 impedance
Allowable Input Operating Range
Type J: -200 to 1200°C or -340 to 2192°F
Type K: -270 to 1370°C or -454 to 2500°F
Type T: -270 to 400°C or -454 to 750°F
Type N: -270 to 1300°C or -454 to 2372°F
Type E: -270 to 975°C or -454 to 1790°F
Type C: 0 to 2315°C or 32 to 4200°F
Type D: 0 to 2315°C or 32 to 4200°F
Type PTII: 0 to 1395°C or 32 to 2543°F
Type R: 0 to 1760°C or 32 to 3200°F
Type S: 0 to 1760°C or 32 to 3200°F
Type B: 0 to 1815°C or 32 to 3300°F
RTD (DIN): -200 to 800°C or -328 to 1470°F
Process V: 0 to 10V
Î(dc) Process I: 0 to 20mA
Control/Alarm Outputs (1 - 4)
User selectable as: on-off, P, PI, PD, PID, heat, cool, alarm
action or retransmit with process output type hardware
Open collector/switched dc
Open collector 42V
Î(dc) maximum@ 0.5A
Switched dc 22 to 28V
Î(dc) limited @30mA
Solid-state relay, Form A, 0.5A @ 24V~(ac) minimum,
264V~(ac) maximum, opto-isolated, without contact
suppression
User-selectable 0-10V
Î(dc), 1K minimum, scalable,
0-20mA @ 800
maximum, scalable
Electromechanical relay. Form C, rated 5A @ 120V~(ac) or
5A @ 240V~(ac) or 5A @ 30V
Î(dc)
Ordering Information
To order, complete the model number on the right with the
information below.
P D - _ _ _ _ - _ _ _ _
Control Type
S = Single channel
D = Dual channel
Auxiliary Inputs
1 = Dual digital inputs
2 = One CT input and one digital input
3 = Dual CT inputs (dual channel only)
Output 1
C = Switched dc, open collector
K = SSR, Form A, 0.5A
F = Universal process
J = Mechanical relay, Form A, 2A
Output 2
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
E = Mechanical relay, Form C, 2A
Output 3
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
F = Universal process (If output 1 is F only)
J = Mechanical relay, Form A, 2A
Output 4
A = None
C = Switched dc, open collector
K = SSR, Form A, 0.5A
E = Mechanical relay, Form C, 2A
On Board Data Logging
0 = None
1 = On board data logging
Custom Options
AA = Watlow logo
BB = No logo
Your Authorized Watlow Distributor Is:
Communications
EtherNet/IP™ with static and dynamic assemblies
PCCC protocol messages
TCP/IP/Ethernet
Modbus™ TCP
Ethernet RJ 45 connector, 10 base T
HTTP interface
DHCP, auto IP or fixed IP address
Dimensions
Width x height x depth, 42 mm x 116 mm x 132 mm
(1.64 in. x 4.56 in. x 5.19 in.)
DIN-rail or chassis mount, DIN-rail spec DIN 5022
35 mm x 7.5 mm (1.38 in. x 0.30 in.)
A