![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/3/f7/3f7f7cb2-6cc4-453b-9ca1-493a559a654e/3f7f7cb2-6cc4-453b-9ca1-493a559a654e-bgf.png)
D7024
Panel Programming
D7024 Operation and Installation Guide
© 2005 Bosch Security Systems Page 65 41740F
7.6.2.2 Dialing Type
Shortcut: 0-PROG, 6-PROG ACC’NTS, 2-PHONE CONTROL
This feature determines what format the panel will use for dialing on each phone line. The tone/pulse setting will first try
tone dialing, and if that fails, will switch to pulse dialing.
Choose Line 1 or Line 2. The display will scroll through the Phone Control options. Press [2] for DIALING TYPE. The
following window will display:
PHONE CONTRO (__)
1- PULSE ONLY
2- TONE/PULSE
3- TONE ONLY
Press the number key that corresponds to your selection. The previous window will be displayed.
7.6.3 Report Steering
Shortcut: 0-PROG, 6-PROG ACC’NTS, 3-RPT STEERING
Different classes of reports can be directed to different phone numbers. Non-supervisory alarms include fire alarms,
waterflow alarms and monitor alarms. Supervisory alarms come from points configured as a supervisory type. Non-
supervisory restorals include fire, waterflow and monitor restorals. Supervisory restorals come only from points configured
as a supervisory type. Trouble reports include all point and system troubles and restorals. Tests include auto tests,
manual tests and off-normal at test reports. The panel allows the special reports “silence”, “reset” and “drill” to be
individually directed.
If any reports are steered to Phone Number 2 (including the default, “phone 2 backup”), a phone
number and account number must be programmed for Phone Number 2. The panel will indicate a
“comm fault” if it sends a report (using phone number 1 parameters) which references
unprogrammed Phone Number 2 parameters.
The display will scroll through the following items:
REPORT STEERING
1- NONSUP ALRM
2- SUPVSRY ALRM
3- NONSUP RSTR
4- SUPVSRY RSTR
5- TROUBLE
6- TESTS
7- SILENCE
8- RESET
9- FIRE DRILLS
Press the number key that corresponds to your selection. The following window will display (with varying headings,
depending on your choice. In this example, non-supervisory alarm is selected):
NONSUP ALRM (___)
1- PHONE 1 ONLY
2- PHONE 2 ONLY
3- PHON 1 AND 2
4- PHN 2 BACKUP
5- NO REPORT
• PHONE 1 ONLY: Report sent to Phone #1 only.
• PHONE 2 ONLY: Report sent to Phone #2 only.
• PHONE 1 AND 2: Report sent to Phone Numbers 1 and 2.
• PHONE 2 BACKUP: Report sent to Phone #1, then to Phone #2 if #1 fails.
• NO REPORT: No report sent.
Press the number key that corresponds with your selection. The previous window will be displayed.