12
TABLE 2 — PHYSICAL DATA 48HE (cont)
BASE UNIT 48HE HD/E/F003 HE/F/H/K/M/N004 HD/E/F/G/H/K/L/M/N005 HD/E/F/G/H/K/L/M/N006
FURNACE SECTION
Rollout Switch CutoutTemp (F)†
195 195 195 195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas — Std* HJE .113...33 HJD .113...33 HJD .113...33
HEE .089...43 HJF .113...33 HJE .113...33 HJE .113...33
— HJF .129...30 HJF .129...30
—
HJH .113...33 HJG .113...33 HJG .113...33
—
HJK.113...33 HJH .113...33 HJH .113...33
—
— HJK .129...30 HJK .129...30
HEM .0 8 9 ...4 3
HJM .102...38 HJL .102...38 HJL .102...38
—
HJN.102...38 HJM .102...38 HJM .102...38
—
— HJN .116...32 HJN.116...32
LiquidPropane — Alt†† HEE .073...49 HJE .089...43 HJD .089...43 HJD .089...43
HJF .089...43 HJE .089...43 HJE .089...43
— HJF .104...37 HJF .104...37
—
HJH .089...43 HJG .089...43 HJG .089...43
—
HJK.089...43 HJH .089...43 HJH .089...43
—
— HJK .102...37 HJK .104...37
—
—
—
—
Thermostat Heat Anticipator Setting (amps)
208/230/460/575 v
First Stage
.14 .14 .14 .14
Second Stage
.14 .14 .14 .14
GasInput (Btuh)
First Stage/Second Stage
HEE 50,000/--- HEE||
50,000/ 72,000
HED|| 50,000/ 72,000 HED|| 50,000/ 72,000
HEF||
82,000/115,000
HEE|| 82,000/115,000 HEE|| 82,000/115,000
— HEF|| 120,000/150,000 HEF|| 120,000/150,000
—
HEH*** —/ 72,000 HEG*** —/ 72,000 HEG*** —/ 72,000
—
HJK***—/115,000 HEH*** —/115,000 HEH*** —/115,000
—
— HEK*** —/150,000 HEK*** —/150,000
—
HEM††† —/ 60,000 HEL††† —/ 60,000 HEL††† —/ 60,000
—
HEN††† —/ 90,000 HEM††† —/ 90,000 HEM†††—/ 90,000
—
— HEN††† —/120,000 HEN††† —/120,000
Efficiency (Steady State) (%) HEE 81 HEE 82.8 HED 82.8 HED 82.8
HEF 80 HEE 81 HEE 81
— HEF 80.4 HEF 80.4
—
HEH 82 HEG 82 HEG 82
—
HEK 80 HEH 81 HEH 81
—
— HEK 80 HEK80
—
HEM 80.2 HEL 80.2 HEL 80.2
HEM 81
HEN81 HEM 81 HEM 81
—
— HEN 80.7 HEN80.7
TemperatureRiseRange HEE 25-55 HED 25-25 HED 25-55
HEE 25-65
HEF 55-85 HEE 35-65 HEE 35-65
— HEF 50-80 HEF 50-80
—
HEH 25-55 HEG 25-55 HEG 25-55
—
HEK 55-85 HEH 35-65 HEH 35-65
—
— HEK 50-80 HEK 50-80
—
HEM 20-50 HEL 20-50 HEL 20-50
—
HEN30-60 HEM 30-60 HEM 30-60
— —
HEN40-70 HEN 40-70
Manifold Pressure (in. wg)
Natural Gas — S td
3.5 3.5 3.5 3.5
LiquidPropane — Alt††
3.5 3.5 3.5 3.5
Maximum Static Pressure (in. wg)
1.0 1.0 1.0 1.0
Field Gas Connection Size (in.)
1
/
2
1
/
2
1
/
2
1
/
2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
450 50
Cutout
428
Reset (Auto.)
320
LOSS-OF-CHARGE SWITCH (LiquidL Ine) (psig)
Cutout
7 3
Reset (Auto.)
22 5
FREEZE PROTECTION THERMOSTAT
Opens (F)
30 5
Closes (F)
45 5
OUTDOOR-AIR INLET SCREENS
Cleanable. Screen quantity and s ize varies with option selected.
RETURN-AIR FILTERS
Throwaway
Quantity...Size (in.)
2...16 x 25 x 2
LEGEND
Bhp — Brake Horsepower
*Stainlesssteel models usesameorificesasequivalent standard unit.
†Indicatesautomaticreset.
**≤72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh heat
input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat
input units have 3burners.
††AnLPkitisavailableasanaccessory. AnLPconversionkitshouldnotbeusedona
low NOx unit because then it can no longer be classified as a Low NOx unit. The
LowNOx requirement only applies to natural gas units.
Three-phasestandard modelshave heatinginputs as shown. Single-phasestandard
models have one-stage heating withheatinginput valuesas showninheatincapac-
itytables.
***Theseunitsdo NOT meettheCalifornia lowNOxrequirements.
†††California SCAQMD compliant low NO
x
modelshave combustion products that are
controlledto 40nanogramsperjouleor less.
48HE,HJ