Name Description Valid Range Initial Value Permission
17 FEATURES Shows the supported resource block options 1 to 4 0x1E Read only
0: Unicode strings
1: Reports
2: Faultstate
3: Soft W Lock
4: Out readback
18 FEATURE_SEL Shows the selected resource block options 1 to 4 0x1E (ALL) Read only
0: Unicode strings N/A
1: Reports
2: Faultstate
3: Soft W Lock
4: Out readback
19 CYCLE_TYPE Indicates available function block execution routines 0 to 2 0 Read only
0: Scheduled
1: Completion of Block Execution N/A
2 : Manufacturer specific N/A
20 CYCLE_SEL Indicates selected function block execution routines 0 to 2 0 Read only
0: Scheduled
1: Completion of Block Execution N/A
2 : Manufacturer specific N/A
21 MIN_CYCLE_T Indicates shortest cycle of which the resource is capable Set by FCS 3200 Read only
22 MEMORY_SIZE Available memory in empty resource (Mcore). Set by FCS 0 Read only
23 NV_CYCLE_T Minimum time interval required to write internal parameters to
non-volatile memory. 0 means only external writes
>=0 Read only
24 FREE_SPACE Memory available for further configuration in FF card 0 to 100% 0 Read only
25 FREE_TIME Block processing time available to additional blocks 0 to 100% 0 Read only
26 SHED_RCAS Time duration at which to give up on computer writes to
function block RCas locations.
>=0 640000 Read only
27 SHED_ROUT Time duration at which to give up on computer writes to
function block ROut locations
>=0 640000 Read only
28 FAULT_STATE Forces output function blocks to the FAULT_STATE condition
if active.
1 to 2 1 Read only
1: clear, 2: active
29 SET_FSTATE Writing a set to this parameter will force FAULT_STATE to be
manually initiated
1: off
2: set
1 to 2 1 Read / Write,
access
controled by
operator
30 CLR_FSTATE Writing a set to this parameter will force FAULT_STATE to be
cleared
1: off
2: clear
1 to 2 1 Read / Write,
access
controled by
operator
31 MAX_NOTIFY Absolute Maximum number of unconfirmed notify messages
possible.
5 5 Read only
32 LIM_NOTIFY Selected Maximum number of unconfirmed alert notify
messages possible
0 to MAX_NOTIFY MAX_NOTIF
Y
Read / Write
33 CONFIRM_TIME Wait time before re-try. 0 = no retry >=0 640000 Read / Write
34 WRITE_LOCK If set no writes accept to clear write lock will be allowed
1: not locked
2: locked
1 to 2 1 Read / Write,
access
controled by
operator
35 UPDATE_EVT Alert generated by any change to the static data
UNACKNOWLEDGED: 0 undefined, 1 acknowledged, 2
unacknowledged
0 to 2 0 Read / Write
UPDATE STATE: 0 undefined, 1 Update reported, 2 Update
not reported
0 to 2 0 Read only
TIME STAMP time 0:00:00 Read only
STATIC REVISION N/A 0 Read only
RELATIVE INDEX N/A 0 Read only
Table 4.1 FieldQ™ Resource Block (Continued)
Index
No.