Specifi cations
Mains voltage 230VAC +10/-15%, 50Hz
Output/nominal voltage typ. 28VDC
Output peak current max. 1.8A
Own current consumption at 24V typ. 70mA (without optional componentries)
Ambient temperature -5°C to +50°C
Relative humidity 95% (no condensation)
Dimensions W × H × D 380 × 480 × 83 (mm)
Colour gray-white, RAL 9002
Weight without accumulator approx. 5kg
Approvals (EN 54-2, EN 54-4) VdS G205023
FT 14/439/04 (Austria),
Part No. 210102
Order name Fire Detection Control Panel BC016-1/INT1
A variety of peripheral devices can be connected to the
fi re detection control panel BC016-1:
• Fire brigade key safe
• Fire brigade control unit
• Acoustic and optical signaling devices
• External protocol printer
• Remote indication unit
• Actuations
• Modules for remote parameterisation and remote
maintenance via computer newtork, modem or GSM
connection
– and much more.