Power supply:
•
Continuous voltage range: 8-35 VDC
•
Brown out voltage < 5 VDC for 2 secs (recovery to 8V)
•
Blackout voltage: 0V for 50mS (from 10V, recovery to 5V)
•
Overvoltage withstand: 50 VDC for 5 seconds (to SAEJ1810 load
dump immunity
•
Reverse voltage withstand: 100 VDC continuous
Current consumption (standby): 50mA
Current consumption (max): 500mA (plus output loads)
DC Inputs:
•
Pressure, coolant temperature
•
Closed to negative DC (±3V) on fault auxiliary and charger faults
•
Remote start positive open from positive DC to start
•
Remote start negative close to negative DC (±3V) to start.
AC Inputs:
•
Magnetic pickup: 3 – 60 VAC, 50Hz – 10 kHz.
•
Generator AC: 600 VAC max (L-L or L-N), 50/60 Hz.
Outputs:
•
Fuel: positive DC (FET switched), 5A max.
•
Crank, preheat: positive DC (FET switched), 2A max.
•
Common alarm, fault lockout negative DC (semiconductor), 300mA max.
•
Generator Hz. meter: 0 – 1 mADC (@ 45–65Hz).
Physical:
•
Operating temperature: -10 to +65
o
C
•
Relative humidity: 95% @ 60
o
C
•
Environmental protection: AS3000U front: IP65, NEMA4
Vibration: ISO 88528 pt.9, & 3 axis 3g
Standard terminal blocks inside the MGC2000 enclosure. Booted type
grommets for a tight seal are available.
MGC-02029B page 2 of 4
16-80 in. (427 mm)
16-80 in. (427 mm)
9.25 in. (235 mm)
7.94 in.
6.81 in.
Hinges for front-opening door option shown in shaded areas.
6.36 in.
9.25 in.
Standard Enclosure Dimensions (all Models)
ASM3000 Controller Specifications
WARNING: Do not bundle AC and DC wiring together. It is required
to use separate conduit runs and keep apart by at least 2 inches.