6F3B0250
Basic Hardware and Function
47
2. Specifications
Functional specifications (cont’d)
Item T1-16 T1-28 T1-40 T1-40S
Real-time clock
/calendar
No Yes,
(
±
30 s/month)
Special I/O functions
(Note)
Hi
h speed counter (2 sin
le or 1 quadrature),
Interrupt input (2 points),
Adjustable analo
re
ister (2 points),
Pulse output (CW+CCW or pulse+direction),
PWM output
Communications
interface
1 port RS-232C (pro
rammer port)
- for Pro
rammer or Computer link connection
-
1 port RS-485
- Pro
rammer
- Computer link
- Data link
- Free ASCII
-
TOSLINE-F10 remote
(by option card)
Debu
support
function
Samplin
trace
(8 devices - 256 times or 1 re
ister - 128 times)
Samplin
trace
(8 devices and
3 re
ister - 256
times)
-
On-line
pro
rammin
-
On-line
EEPROM write
NOTE
(1) The input specification of the T1-16 (AC power type) is dry contact input,
which supplies the power for input signals (24 Vdc) from the unit.
Other types are DC input, which requires external power for input signals.
(2) High speed counter, interrupt input, pulse output and PWM output are
available in the DC input types.
(3) High speed counter and interrupt input cannot be used simultaneously.
(4) Pulse output and PWM output cannot be used simultaneously.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net