Expandable battery
runtime
Yes, with optional external battery packs
DC system voltage 240V DC
Typical battery
lifespan
4-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
VOLTAGE REGULATION
Voltage regulation
description
On-line, double-conversion process give this UPS the ability to maintain output voltage within +/-2% of selected
nominal voltage at all times
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 276V AC, regulating output within
2% of selected nominal
Brownout correction Maintains continuous operation without using battery power during brownout / undervoltage conditions to 156VAC,
regulating output within 2% of selected nominal
LEDS ALARMS & SWITCHES
Front panel LEDs 6 LED DISPLAY: line power, bypass, inverter, charger, output AC and battery operation. SELECTABLE LCD
DISPLAY: input/output voltage, Hz, battery voltage and charge level and detailed warnings regarding all major UPS
functions
Alarms Multi-function audible alarm offers notification of UPS start, backup operation, low battery, overload, UPS fault, inverter
fault, DC bus fault, overtemperature, remote shutdown, shutdown imminent and shutdown complete
Switches Includes main power off/on switch, plus 2 switches to set and execute scrollable LCD functions
SURGE / NOISE SUPPRESSION
AC surge suppression 480 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 256
Shipping weight (kg) 117
Unit weight (lbs) Power Module (42 lb), Transformer Module (57 lb), Battery Module (92 lb)
Unit weight (kg) Power Module (20 kg), Transformer Module (26 kg), Battery Module (42 kg)
Unit Dimensions
(HWD/in)
Power Module (5.25 x 17.5 x 26 in), Transformer Module (3.5 x 17.5 x 21 in), Battery Module (3.5 x 17.5 x 22.5 in)
Unit Dimensions
(HWD/cm)
Power Module (13.3 x 44.5 x 66 cm), Transformer Module (8.9 x 44.5 x 53.3 cm), Battery Module (8.9 x 44.5 x 57.2 cm)
Material of
construction
Steel
Form factors
supported
Rack (7U)
Cooling method Built-in cooling fan
Battery Access User replaceable, hot swappable external battery pack
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit, -15 to +50 degrees Celsius
Operating
Temperature
+32 to +104 degrees Fahrenheit, 0 to +40 degrees Celsius
Line mode BTU/hr.
(Max.)
1937.3
COMMUNICATIONS