3 Communication (continued)
3.1 Setting EEPROM on the NH-M Board
3.1.1 Polling and Updating EEPROM
WARNING: This procedure must be performed in bypass mode (see section 1.6).
Instructions for polling and updating the EEPROM are as follows (Figure 3.1.1a):
a) Link the UPS with a PC via the RS232 port
b) Run the program “NH_SYS_V1_3B1030.exe
c) Click the “EEPROM” icon
d) Select the PC COM Port and click “Open COM Port
e) Click Polling” to download the EEPROM data from the UPS.
f) Save the fi le to ensure that you have the values in case they are needed later
g) After setting the data, click “Update All” and wait for the procedure to complete itself
Fig 3.1.1a
EEPROM