35
5.5.2 Connection of the Battery Cubicle PROTECT 1. BP20
Fig.: Rear view of the PROTECT 1.BP20 with cover removed.
The battery cubicle is supplied with a separate battery string
and separately enclosed battery fuses for safety and transport
protection reasons. Please also note the separate
documentation enclosed with the battery cubicle.
After the battery cubicle has been removed from the pallet,
first remove the rear cover. Now create the electrical
connections with the enclosed connectors (see also circuit
diagram X1/X2/X3)
and
The PROTECT 1.100 is connected to the UPS at the socket
using the special battery connection cable enclosed with
the UPS, and in the case of the PROTECT 1.150 or
PROTECT 1.200 with the battery connection cables enclosed
with the battery cubicle at the terminals. Make sure to observe
the terminal block assignment concerning the correct polarity
"+" and "-" as well as an earth-fault- and short-circuit-proof
routing, in addition to the proper earthing of the battery
cubicle.