American Power Conversion AP9554 Power Supply User Manual


 
8
Operation
Overview
!
Inlet
IEC 320 C20 inlet (16A @ 240V; 20A @ 120V)
used with detached power cord (supplied)
.
"
Ground
stud
6-32
ground stud that can be used to ground the
unit to the enclosure
#
Circuit
Breaker
When the button is extended, the circuit breaker
is tripped, the
PDU
is overloaded, and at least
one piece of equipment needs to be unplugged.
The circuit breaker is rated to trip at the same
overload as most home and office utility service
branch protectors (
20A
).
$
Outlets
Fourteen IEC 320 C13
outlets
(
10A @ 240V; 15A @ 120V
)