American Power Conversion RT-UXICH Power Supply User Manual


 
10
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT
ACCESSORY CARDS OR TERMINAL MODE.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
High Bypass Point +10% of
output voltage
setting
+5%, +10%, +15%,
+20%
Maximum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Low Bypass Point -30% of output
voltage setting
-15%, -20%, -25%, -30% Minimum voltage that the UPS
will pass to connected
equipment during internal
bypass operation.
Output Voltage 230 VAC 220, 225, 230, 240 VAC Allows the user to select the
output voltage.
Output Frequency Automatic
50 ± 3 Hz or
60 ± 3 Hz
Automatic
50 ± 3 Hz,
50 ± 0.1 Hz
60 ± 3 Hz
60 ± 0.1 Hz
Sets the allowable UPS output
frequency. Whenever possible,
the output frequency tracks the
input frequency.
Number of Batteries 1 Number of Connected
Batteries
Defines the number of
connected batteries for proper
run time prediction.
Default setting of 1 = 1920 VAh
(192 V x 10 Ah)
Setting of 2 = 3840 VAh, etc.