American Power Conversion SUOL1000UXI Power Supply User Manual


 
990-1137, 3/02 8
USER CONFIGURABLE ITEMS
NOTE: SETTING THESE ITEMS REQUIRES SOFTWARE, OPTIONAL HARDWARE, OR
CONFIGURATION IN TERMINAL MODE.
FUNCTION
F
ACTORY
DEFAULT
USER SELECTABLE
CHOICES
D
ESCRIPTION
Automatic Self-
Test
Every 14 days
(336 hours)
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
This function sets the interval at which the
UPS will execute a self-test. Refer to your
software manual for details.
UPS ID UPS_IDEN Up to eight charac-
ters to define the
UPS
Use this field to uniquely identify the UPS
for network management purposes.
Date of Last Bat-
tery Replacement
Manufacture
Date
Date of Battery
Replacement
Reset this date when you replace the battery
pack.
Minimum Capacity
Before Return from
Shutdown
0 percent 15, 25, 35, 50, 60,
75, 90 percent
The UPS will charge its batteries to the
specified percentage before return from a
shutdown.
Duration of Low
Battery Warning
2 minutes 5, 7, 10, 12, 15, 18,
20 minutes
This function sets the time before shutdown
at which the UPS issues a low battery
warning. Set it higher than the default if the
operating system needs more time for shut-
down.
Alarm Delay After
Line Fail
5 second delay 30 second delay, At
Low Battery Condi-
tion, No Alarm
Set the alarm delay to avoid alarms for
minor power glitches.
Shutdown Delay 20 seconds 0, 60, 120, 240, 480,
720, 960 seconds
This function sets the interval between
when the UPS receives a shutdown com-
mand and when shutdown occurs.
Synchronized
Turn-on Delay
0 seconds 20, 60, 120, 240,
480, 720, 960 sec-
onds
The UPS will wait the specified time after
the return of utility power before turn-on
(for example, to avoid branch circuit over-
load).
Output Voltage
Setting
230 VAC 240, 220, 225 VAC Nominal output voltage setting.
High Transfer
Point
+ 10% of output
voltage setting
+5%, +15%, +20% Maximum voltage that the UPS will pass to
the load during internal bypass operation.
Low Transfer Point -30% of output
voltage setting
-20%, -25%,
-15%
Minimum voltage that the UPS will pass to
the load during internal bypass operation.