APC 40004075KVA208Vi Power Supply User Manual


 
Specications
Environmental Recommendations
Recommended Environment 20° to 25°C (68° to 77°F.); 50% relative humidity; computer room or other
temperature, and humidity-controlled environment
Operating Temperature to 30°C (32° to 86°F) except battery
Storage
-20° to 40°C (-4° to 113°F) except battery
Humidity Up to 90% non-condensing (operating)
Altitude Sea level to 3,000 feet without derating
Acoustic Noise 69 dBA at rated load as measured 3 feet from the front of the UPS cabinet.
Electrical Specications
Output Power Rating (0.8) PF
40 kVA 50 kVA 65 kVA 75 kVA
UPS Voltage (input/output) 208/208 208/208 208/208 208/208
Input/Output Requirements &
Frequency
Three phase, Three wire + N + G, 60Hz
Input Phase Rotation A,B,C Clockwise
Input Power Factor
>.98
Input Current 102A 127A 166A 191A
Maximum Input Current (at low line
—15%)
120A 150A 195A 225A
Bypass Current 111A 139A 180A 208A
Output Current 111A 139A 180A 208A
Battery Voltage 198 VDC End Voltage 240VDC Nominal 282VDC
Max. Maintenance Voltage
Max. Battery Current at Nominal
Battery Voltage (240 VDC at 100%
load)
157A 196A 255A 294A
Max. Battery Current at Nominal End-
Voltage (198 VDC at 100% load)
190A 238A 309A 357A
Battery Disconnect Circuit Breaker
Rating
250A 400A
Input, Bypass, and Maintenance Bypass
(optional) Switch Rating
150A 250A
Input Fuse Rating
200A 300A
Output Isolation Circuit Breaker Rating
175A 300A
NOTE: Interrupted Transfer to Bypass Source:
If the bypass source is beyond the conditions stated below, the UPS will make an interrupted transfer (not more
than 100 msec. in duration).
1. Bypass voltage greater than +15%, —15% from the UPS rated output voltage.
2. Bypass frequency greater than ±2 Hz from the UPS rated output frequency.
990–3964–001
MGE Galaxy 4000 40–75 kVA 208 V
3