Unitary UPS (continued)
Load on Mains 2
Normal: bit 4C4 = 0
Danger: bit 4C6 = 1
Downgraded: bit 4C5 = X (N/A)
Load on battery: bit 4C7 = X (N/A)
Q1 indifferent: bit 40E = X (N/A)
Rectifier/charger indifferent: bit 408 = X (N/A)
QF1 indifferent: bit 400 = X (N/A)
Inverter disconnected: bit 484 = 0
Q5N closed: bit 498 = 1
Q3BP open: bit 497 = 0
Q4S closed: bit 496 = 1
SS closed: bit 499 = 1
K2S closed (if available): bit 494 = 1
Normal: bit 4C4 = 0
Danger: bit 4C6 = 1
Downgraded: bit 4C5 = X (N/A)
Load on battery: bit 4C7 = X (N/A)
Q1 indifferent: bit 40E = X (N/A)
Rectifier/charger indifferent: bit 408 = X (N/A)
QF1 indifferent: bit 400 = X (N/A)
Inverter connected indifferent: bit 484 = X (N/A)
Q5N open: bit 498 = 0
Q3BP closed: bit 497 = 1
Q4S indifferent: bit 496 = X (N/A)
SS indifferent: bit 499 = X (N/A)
K2S indifferent: bit 494 = X (N/A)
Load on bypass