APC 60-80kW Power Supply User Manual


 
78 Installation Guide APC Silcon 60-80kW 400V UPS
990-4051
Appendix
9.0 Appendix
9.1 Table 1. Installation Planning Data
Main Input
Breaker
Field
Wiring*
Battery Bank**
UPS Module
Service Bypass Panel
Field
Wiring
Output
Breaker
*
** Internal Batteries available for 40kW units and smaller
*
*
Q1
Q2
Q3
* Not supplied by APC
Installation Planning Data
APC Silcon Series
AC Input Battery System DC AC Output
Min. Input Input Full I
Nom
I
Max
Load side Heat
Power rating Source P (kW) I (A) Cable Overcurrent V
n
load Disch Disch I
n
Overcurrent Dissipation
kW kVA Pf V Hz Nom. Max. Nom. Max. (per phase) Protection* (Vdc) P(kW) (A) (A) (A) Protection* (kW)
60 60 1 380
400
415
50/60 66.1 76.6 105.1
100.5
96.4
115.6
110.6
106.0
50mm
2
125 A 2x384 62.2 81 96 90.9
87.0
83.3
100 A 2.4
80 80 1 380
400
415
50/60 87.9 101.7 139.5
133.5
127.9
153.5
146.8
140.7
70mm
2
160 A 2x384 82.9 108 128 121.2
115.9
111.1
125 A 2.9
COLUMN 1a 1b 1c 1d 1e 1f 1g 1h 2a 2b 2c 2d 3a 3b 4a
NOTES 3 4 1 2 9 5, 6, 13 8 12 10 11 6, 7 13
* Provided by others