APC BC300 Power Supply User Manual


 
Specifications
990-1403
User Guide APC BC300 Series 40kW 208/450/480V UPS 29
8.0 Specifications
For a complete list of specifications, see the APC BC300 Series Installation Guide.
Table 7: General Specifications
Utility tolerance +10%, 15% (programmable)
Bypass tolerance ±10% (programmable)
Input frequency ±6% (programmable) 60 Hz
Output frequency
- utility synchronized:
- free running:
60 Hz ±6%
60 Hz ±0.1%
Current distortion 0-5%
Tolerance
- symmetrical load:
- asymmetrical load:
- load step 0-100:
±1%, static.
±3%, static. (100% imbalance, provided
output current rating is not exceeded.)
±5%.
Distortion (linear load) 0-3%
Overload capacity
- normal operation, 1 minute
- normal operation, 10 minutes
- battery operation, 1 minute
- battery operation, 10 minutes
250%
150%
150%
125%
Audible noise (dBa) dBa
Maximum Humidity (non condensing) 95%
Efficiency 95%