APC LX Power Supply User Manual


 
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
APC Symmetra LX
GUIDE SPECIFICATIONS FOR
4kVA-16kVA
Uninterruptible Power System
PART 1 - GENERAL
1.1 SUMMARY
A. This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS.
B. The UPS shall utilize modular power protection technology designed to allow internal
redundancy, scalability of power and runtime, and fast mean time to repair (MTTR).
The UPS should be configured from five basic components- UPS frames, extended run
battery frames (XR frames), power modules, battery modules, and intelligence modules.
UPS and XR frames should be capable of shipping with modules installed. XR frames
should be capable of communicating battery and runtime status to intelligence modules.
Power, battery, and intelligence modules should be hot-swappable and user-replaceable
for fast MTTR.
C. Configuration Specifics:
1. The UPS frame(s) should be capable of the following configurations:
____4-8kVA N+1 Redundant Tower
____4-16kVA N+1 Redundant Tower
____4-16kVA N+1 Redundant Tower with nine (9) extra Battery Module slots
____4-8kVA N+1 Redundant 13U Rack-mount
____4-16kVA N+1 Redundant 19U Rack-mount
2. The system power train shall be comprised of hot-swappable, user-replaceable
3.2kW/4kVA and 10% Battery charger circuit power modules, which shall
operate in parallel, and be configurable for N+1 redundant operation at rated
load.
3. The system shall also include a field-replaceable internal automatic and manual
bypass system module, field-replaceable output power distribution panels,
removable input/output wiring tray, standard redundant intelligent modules,
battery disconnects, an LCD interface display, EPO, and an integrated UPS
network management card with temperature monitoring.
D. In addition, this specification describes the performance, functionality, and design of
the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery
Systems, and connectivity solutions.