APC MW II Power Supply User Manual


 
19Symmetra MW II 1200 kW 3 x 400/230 V Installation - 990-1979E-001
AC Output
AC Input External Bypass SSW
The External Bypass SSW is designed to accommodate a continuous overload of 25%.
Heat dissipation
37.1 kW / 126.7 kBTU/hr (note 6).
Notes
1. Nominal (Nom): Input current based on rated load, nominal input voltage and fully charged
batteries.
2. Current limitation is maximum allowed via electronic current limiting and is based on full battery
recharge + nominal load and -10% input voltage.
3. Nominal battery voltage assumed to be 2.0 volts/cell (lead technology).
4. Nominal Battery Discharge current based on rated load, and nominal Battery voltage.
5. Maximum Battery Discharge current based on rated load at end of Discharge.
6. Heat dissipation calculated at rated load capacity.
7. This current is at 125% of rated load and is electronically current-limited to a maximum of 10
minutes. This value is only provided so the engineer can ensure that the selected AC output
circuit overcurrent device’s time-current characteristic will support this condition.
8. At 380 V, nominal output is reduced from 200 kW to 180 kW in each section.
AC Output
Voltage 380 V
Current Nom (note 8) 1641 A
Max (note 7) 2051 A
Voltage 400 V
Current Nom 1732 A
Max (note 7) 2165 A
Voltage 415 V
Current Nom 1669 A
Max (note 7) 2087 A
AC Input External Bypass SSW
External Bypass SSW Max Input Current (100% load)
380 V 1641 A
400 V 1732 A
415 V 1669 A