APC PDPM150L6F Power Supply User Manual


 
19150/175kw Modular PDU Installation
Specifications
AC Input
Model
PDPM150G6F PDPM150L6F PDPM175G6H
Nominal voltage 480V, 3W +G 600V, 3W +G 480V, 3W + G
Frequency 60 Hz 60 Hz 60 Hz
Maximum
continuous
current
180 A 150 A 214 A
Nominal current 178 A 141 A 214 A
Recommended current rating of input circuit breakers
Mains Input
1
(A) 225 200 300
Inrush currents
Inrush Current
2
2000 1500 2100
1
Standard circuit breakers are rated to carry 80% of their current rating
continuously.
2
The supply overcurrent protective device must be able to handle the listed
transformer inrush currents.
AC Output
Model
PDPM150G6F PDPM150L6F PDPM175G6H
Nominal voltage 208Y/120V,
3W + N + G
208Y/120V,
3W + N + G
415Y/240V,
3W + N + G
Maximum continuous current 400 A 400 A 243 A
Full load rating 144 kW @ 208V 3
PH
144 kW @ 208V 3
PH
175kW @ 415V 3 PH
Power distribution module
(PDM)
208/120V, 3-pole
modules
208/120V, 3-pole
modules
415/240V, 3-pole
modules
Power distribution poles
available
72 72 72
Maximum number of PDMs 24 24 24