APC SMC10002U Power Supply User Manual


 
Smart-UPS C 1000/1500/2000/3000 VA 120/230 Vac Rack-Mount 2U6
Sensitivity adjustment settings
The UPS detects and reacts to line voltage distortions by transferring to battery backup power to protect
connected equipment. In situations where the connected equipment is too sensitive for the input voltage
level it is necessary to adjust the transfer voltage.
1. Connect the UPS to a AC power source. Be sure the UPS is turned off.
2. Place the unit in Configuration Mode, as described in page 9.
3. Use the Sensitivity Setting option to set the transfer voltage range.
When the UPS is in Configuration Mode, the Sensitivity bar graph icons display the sensitivity level
setting. Refer to the examples here as a reference.
Status Indicators
Display panel features
Low sensitivity Medium sensitivity High sensitivity (Default)
120 Vac: 97-136 Vac 120 Vac: 103-130 Vac
120 Vac: 106-127 Vac
230 Vac: 195-265 Vac 230 Vac: 203-257 Vac 230 Vac: 207-253 Vac
Use this setting with equipment
that is less sensitive to fluctuations
in voltage or waveform distortions.
Use this setting under normal
operating conditions.
Use this setting when connected
equipment is sensitive to any
minor fluctuations in voltage or
waveform distortions.
120 Vac 230 Vac
On Line/On Battery LED Display interface
POWER ON/OFF button DISPLAY button
Site Wiring Fault/System Fault LED
MUTE button
Note: Refer to “Feature Reference Guide” on page 9 in this manual for a
detailed description of the front panel buttons and icons.
su0740d
su0740c