APC SMX2200RMLV2U Power Supply User Manual


 
Smart-UPS X 2000/2200/3000 VA 8
Configuration
UPS Settings
Start-up Settings
Use the display interface to configure these settings at initial start-up. The UPS will prompt for a
response to each setting, if no response is given, the default setting will be used.
Note: The unit will not turn on until all of these settings are entered.
Function Factory Default Options Description
Language English • English
•French*
•German*
• Spanish*
• Italian*
• Portuguese*
The language for the display interface.
*Language options will vary by model.
Output
Voltage
Low Voltage: 120 V • 100
•110
•120
•127
Set the output voltage setting while the UPS is in
Standby mode.
High Voltage: 230 V • 200
•208
•220
•230
•240
Input Power
Quality
Good • Good
•Fair
• Poor
Select the quality of input utility power.
• If Good is selected, the unit will go on battery
power more often to provide the cleanest power
supply to the connected equipment.
• If Poor is selected, the UPS will tolerate more
fluctuations in power and will go on battery power
less often.
If unsure of the local power quality, select Good.
Menu Type Standard Standard or
Advanced
The advanced menus include all parameters. The
Standard menus display a limited set of menus and
options.
Date UPS manufacture
date + 90 days
mm-yyyy Enter the current date.