APC SMX2200RMLV2U Power Supply User Manual


 
Smart-UPS X 2000/2200/3000 VA 12
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC).
NMC IP Address Mode
NMC Default Gateway
Turn Off Delay 90 sec Set the value in
seconds
The amount of time that the Switched Outlet
Groups will wait between receiving the command
to turn off and the actual shut down.
Reboot Duration 8 sec Set the value in
seconds
The amount of time that the Switched Outlet
Groups must remain off before it will restart.
Minimum Return
Time
0 sec Set the value in
seconds
The amount of battery runtime that must be
available before the Switched Outlet Groups will
turn on again after a shutdown.
Load Shed On
Battery
Disabled • Shutdown with
Delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
When the unit switches to battery power, the UPS
can disconnect power to the Switched Outlet
Groups to save runtime.
Configure this delay time, use the
LOAD SHED
T
IME WHEN ON BATTERY setting.
Load Shed Time
when On Battery
Disabled Set the value in
seconds
The amount of time the outlets will function on
battery power before they will turn off.
Load Shed On
Runtime
Disabled • Shutdown with
delay
• Shutdown
immediately
• Turn off
immediately
• Turn off with delay
• Disabled
Configure this time using the
LOAD SHED
R
UNTIME REMAINING setting.
Load Shed On
Runtime
Remaining
Disabled Set the value in
seconds
When the remaining runtime reaches this level,
the Switched Outlet Groups will turn off.
Load Shed on
Overload
Disabled • Disabled
• Enabled
In the event of an overload (greater than 105%
output), the Switched Outlet Groups will
immediately turn off to conserve power for
critical loads. The Switched Outlet Groups will
only turn on again with a manual command.
Function Factory Default Options Description