APC SUA2200 Power Supply User Manual


 
12 Smart-UPS XL 3U Rack Mount 2200/3000 VA 120/230 Vac; 3000 VA 100/200 Vac User Manual
Configuration
Connect the Emergency Power Off option
The Emergency Power Off (EPO) option is a safety feature that will immediately remove power to all
connected equipment. When the EPO button is pushed, all connected equipment will immediately turn off and
will not switch to battery power.
Adhere to all national and local electrical codes when wiring the EPO.
1. Use the EPO terminal block supplied with the UPS.
2. Insert one wire from the EPO cable into the +24 terminal, and one wire into the IN
terminal of the EPO terminal block.
3. Secure the connection by tightening the screws on the EPO terminal block.
4. Plug the terminal block into the UPS.
The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV circuits.
The EPO interface monitors circuits that have no determined voltage potential. Such closure circuits
may be provided by a switch or relay properly isolated from the utility. To avoid damage to the UPS, do
not connect the EPO interface to any circuit other than a closure type circuit.
Use one of the following cable types to connect the UPS to the EPO switch.
CL2: Class 2 cable for general use.
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).
For installation in other countries: Use standard low-voltage cable in accordance with national and
local regulations.
Low Transfer Point 100 V models:
92 Vac
86 Vac
88 Vac
90 Vac
92 Vac
To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low
transfer point lower if the connected equipment
can tolerate this condition.
120 V models:
106 Vac
97 Vac
100 Vac
103 Vac
106 Vac
200 V models:
184 Vac
173 Vac
176 Vac
180 Vac
184 Vac
230 V models:
208 Vac
196 Vac
200 Vac
204 Vac
208 Vac
Output Voltage
230 V models 230 Vac
220 Vac 240 Vac
230 V models only: Sets the UPS output
voltage.
Function
Factory
Default
User Selectable
Choices Description