9
N
OTE: SETTINGS ARE MADE THROUGH THE SUPPLIED POWERCHUTE SOFTWARE OR
THE NETWORK INTERFACE CONNECTION. REFER TO THE SOFTWARE HELP GUIDES FOR DETAILS.
FUNCTION
F
ACTORY
D
EFAULT
U
SER SELECTABLE
CHOICES
D
ESCRIPTION
High Transfer Point 120 V:
127 VAC
230 V:
253 VAC
120 V:
127, 130, 133, 136 VAC
230V:
253, 257, 261, 265 VAC
If the utility voltage is usually high and the
connected equipment is specified to operate
with input voltages this high, set the high
transfer point higher to avoid unnecessary
battery usage.
Low Transfer Point 120 V:
106 VAC
230 V:
208 VAC
120 V:
106, 103, 100, 97 VAC
230 V:
208, 204, 200, 196 VAC
If the utility voltage is usually low and the
connected equipment is specified to operate
with input voltages this low, set the low
transfer point lower.