5: STORAGE, MAINTENANCE, SHIPPING, AND SERVICE
Storage
Store the UPS covered in a cool, dry location, with the battery fully charged.
At -15 to +30 °C (+5 to +86 °F), charge the UPS battery every six months.
At +30 to +45 °C (+86 to +113 °F), charge the UPS battery every three months.
Battery Module Maintenance
The UPS battery life differs based on usage and environment. Consider replacing the battery every three years.
This UPS has an easy to replace, hot-swappable battery. Replacement is a safe procedure, isolated from electri-
cal hazards. You may leave the UPS and connected equipment on during the replacement procedure.
Note: Upon battery disconnection, equipment is not protected from power outages.
See your dealer or contact APC (see Contact Information) for information on replacement batteries.
Refer to Rack-Mount the UPS and Connect the Battery for instructions on battery removal and replacement.
Power Processing Module Replacement
Press and hold the black switch (see loca-
tion designation below) to the right, while re-
moving the power processing module.
*Reverse steps 1-4 for installation of the new module.