Chapter 1. Introduction
26
No. Item Description
1 Power Outlets* 28 in total (24 x IEC 320 C13 + 4 x IEC 320 C19)
Bank 1: Outlet 1–14: 12 C13; 2 x C19
Bank 2: Outlet 15–28: 12 x C13; 2 x C19
2 Port and LED Panel The Port and LED panel contains:
Readout Section and LEDs
Environmental Sensor Ports
LAN Port
Door Sensor Port
Reset Switch
Full details of this section are provided on
page 23.
3 Circuit Breaker As a safety measure, if there is an overcurrent
situation regarding the device’s power, the circuit
breakers will trip. Press the button to recover
normal operation.
Warning: See Resetting the Circuit Breaker,
page 79 for important information about resetting a
tripped circuit breaker.
4 Power Cord The power cord that connects the unit to an AC
power source plugs into this socket.
B models connect to a NEMA L6-30P source
G models connect to an IEC 60309 32A source
5 Output Power Indicator This LED lights steady to indicate output power for
the related bank.