Mounting Guidelines
The Model 071014 Switching Neutral Manual Transfer
Switch is enclosed in a NEMA Type 1 enclosure
suitable for indoor use ONLY.
The Model 071017 Manual Transfer Switch is enclosed
in a NEMA Type 3R enclosure suitable for
indoor/outdoor use.
Guidelines for mounting the Switching Neutral Manual
Transfer Switch include:
• Model 071017 Switching Neutral Manual Transfer
Switch must be installed with minimum NEMA 3R
hardware for conduit connections.
• Install switch on a firm, sturdy supporting structure.
• Ensure enclosure is level and plumb. This can be
done by placing washers between switch enclosure
and mounting surface.
• NEVER install switch where any corrosive substance
might drip onto enclosure.
• Protect switch at all times against excessive moisture,
dust, dirt, lint, construction grit and corrosive vapors.
The typical installation of the Switching Neutral Manual
Transfer Switch is depicted in Figure 2. Discuss layout
suggestions/changes with the owner before beginning
the system installation process.
INSTALLATION
7
Switching
Neutral Manual
Transfer Switch
Main
Distribution
Panel
Figure 2 — Typical Switch Mounting
Model 071014 shown